3D model of a METALOQ module frame
Documentation

Frame types

One connection logic, many sizes and shapes.

In brief

A parametric family

The frame family is parametric: the connection logic stays the same while individual parts are made longer or stronger as needed. “Standard” describes what the tooling is already set up for, not a limit on capability. Specifying the standard frame gives the fastest fabrication.

Fifteen different frame shapes and sizes built from the same components
A sample of frame variants built from the common set of components.

The standard frame

Column4 × 12 in (100 × 300 mm), 1/4 in (6 mm) wall
Rim floor beam3 × 10.5 in (75 × 265 mm), 1/4 in (6 mm) wall
Rim ceiling beam3 × 6.5 in (75 × 165 mm), 1/4 in (6 mm) wall
Floor joist10 in (250 mm) deep, 16 gauge
Ceiling joist6 in (150 mm) deep, 16 gauge
Module floor area350 sq ft
Self-weight42 psf, of which the frame is 14 psf
Fire rating1 to 2 hours, by assembly
Stackable height1 to 10 storeys, depending on location and seismic category
View down the inside of a standard module frame

Catalogue

28 ft standardHotel and multifamily module
40 ft ADUDetached accessory dwelling
Heavy mechanicalService-dense modules, with a larger column
L-shaped ADUCorner sites
Stair towerEgress core
ElevatorElevator shaft

What can vary

  • Size. Columns and beams are cut to length. Rim beams span up to 26 ft; longer modules add an intermediate column. Height is normally set by the shipping route.
  • Column spacing. Intermediate columns are placed to suit the interior layout.
  • Bracing. Braces are placed around windows and doors.
  • Floor openings. Openings for stairs, shafts and service risers are framed into the joist layout.

Stairs

Stairs can be supplied from the same manufacturing process as the frame, with or without guardrails and handrails, and installed in the module at the factory or on site. A stair built into the module also gives the setting crew access to the next level, which speeds up the build.

A three-storey stack of stair modules with the stair flights shown in bronze

Ten storeys, assessed

Ten storeys is the tallest METALOQ building assessed to date. JEROL Technologies assessed a ten-storey building of 100 modules in North York, Ontario, against the Ontario and National building codes. The assessment demonstrates the system on one building and one site. It is not a rating for the product generally, and each building requires its own engineering.

Taller buildings

Above the height the module frame can resist on its own, a separate core or tower carries the lateral load. A very tall METALOQ building is designed as a stack of mid-rise buildings, each standing on its own structural shelf, so a standard six-storey frame is reused all the way up.

Study of two tall towers made of six-storey METALOQ stacks set on structural shelves
Concept study by METALOQ and Skyhook, not an engineered design.

Chapter 2 in full

METALOQ Documentation v1.0, pages 15–22. Select a page to enlarge it.

2 Frame Types

Frame Types Catalogue

2 Frame Types, page 15
Page 15Enlarge
Read page 15 as text

CHAPTER

Frame Types

The METALOQ frame family is parametric: while the connection logic remains consistent, the individual parts can be made stronger as needed. This chapter defines the standard frame, the configuration recommended by default, and documents each mode of variability. “Standard” refers to tooling setup, not a capability limit: any size in the family can be fabricated, and the standard configuration is simply the one the shop drawings, CNC, laser-cutting, and brake-forming are already set up for (see §2.1). Tables throughout this manual highlight the standard configuration in amber to encourage its use.

Frame Types Catalogue

The Skyhook / Nelson Parametrics model inventory currently contains the following frame variants. Engineering data for each is tabulated in Chapter 3.

TAG STATUS VARIANT BAYS (L × W) TYPICAL USE

F-28 Standard 28′ standard 2 × 1 Hotel / multifamily module

F-ADU Off-the-shelf 40′ ADU 3 × 1 Detached accessory dwelling

F-HMD Off-the-shelf Heavy mechanical 2 × 1 MEP-dense, increased column

F-L Off-the-shelf L-shaped ADU L Corner-site ADU

F-ST Off-the-shelf Stair tower 1 × 1 Egress core

F-EL Off-the-shelf Elevator 1 × 1 Elevator shaft

The table shows a sample of the types available; contact True Volumetric Corporation for more information.

DESIGN RULE Specify standard wherever you can

For the fastest fabrication, start with the standard frame: the system is already built for it. It unlocks the full catalogue of tested connections, seismic strategies and fire-rated assemblies without additional work. Its components are inventoried and repeatable, ordered and picked like any other catalogue item. It also runs on part programs that already exist, so it is made by an automated process. Every departure from the standard needs engineering, fabrication set- up and new details; once these are complete, the new configuration can be promoted to off-the-shelf status.

2.1 Standard Frame

2.1 Standard Frame, page 16
Page 16Enlarge
Read page 16 as text

2 . 1 Standard Frame

MEMBER SYMBOL STANDARD OPTIONAL

Column CLM 4×12 / 100×300 mm, ¼″ / 6 mm wall 4×4, 4×6, 4×8, 4×10, 4×12

Rim floor beam RMJ-L 3×10.5 / 75×265 mm, ¼″ / 6 mm wall thicker wall, or 3×12.5 depth

Rim ceiling beam RMJ-U 3×6.5 / 75×165 mm, ¼″ / 6 mm wall thicker wall, or 3×8.5 or 3×10.5 depth

Floor joist JST 10″ / 250 mm deep, 16 g / 1.6 mm (0.061″) 8″ or 12″ deep, or I-span type

Ceiling joist JST 6″ / 150 mm deep, 16 g / 1.6 mm (0.061″) 8″, 10″ or 12″ deep, or I-span type

Strap bracing BRC 16 g / 1.6 mm strap, outside cavity see seismic ladder

BASELINE STATS

METRIC STANDARD FRAME UNIT

Self-weight 42 (14 frame only) psf

Floor stiffness (L/Δ) 360 minimum; 720 under tile ratio

Stackable height 1–10, depends on location and seismic category storeys

Module floor area 350 ft²

Fire rating (assembly) 1–2 hour, see Assemblies hr

2.2 Modes of Variability and Measurement

2.2.1 W × L × H — adjusting width, length and height

2.2.2 Wall openings and bracing

2.2.3 Floor openings and bracing

2.2.4 Volumetric bracing

2.2 Modes of Variability and Measurement, page 17
Page 17Enlarge
Read page 17 as text

2 . 2 Modes of Variability and Measurement

The standard frame is a fixed set of components, not a fixed size. Four aspects of the frame are adjustable:

• Size: The columns and beams are cut to the required length.

• Intermediate Column Spacing: The spacing is set to suit the interior layout.

• Bracing: Braces are placed around windows and doors.

• Floor Openings: Openings are provided for stairs, shafts, and MEP risers.

W × L × H — adjusting width, length and height

The frame extends along each of the three axes to any shippable size, while the connection details remain the same. What varies is the cut length of members that are otherwise identical. This is why the family absorbs a dimensional change without a new engineering cycle: the geometry changes, but the connection details do not. Member length is limited only by the manufacturing equipment:

• Rim beams span up to 26′. For a longer module, an intermediate column is added and supports a second beam of up to 26′.

• Column height is not limited by fabrication. It is normally set by the transportation height of the shipping route.

Wall openings and bracing

An opening in a wall is accommodated by the same family of components. Walls can include doors, windows, and corridor openings. These openings are framed according to stud layout practice.

Bracing is then placed to suit those openings. The plate that connects the brace to the frame can be located anywhere along the rim beams, but a column is typically required at each end of the braced bay. See §3.2 and §3.3 for columns. See §3.7 for braces.

Floor openings and bracing

Many different floor openings can be accommodated by the joist layout. Openings through the floor and ceiling for stairs, shafts, and MEP risers are reinforced with trimmer joists or a mid-span rim beam. See §3.5 for joists.

Volumetric bracing

Bracing is designed for two load cases: transport of the individual module, and the building loads at that module’s position in the stack. Both govern the specification.

DESIGN RULE Brace for the worst case, use one frame

In a mass-customized product line, standardizing on the most demanding case is often more efficient than stocking several SKUs. A column can be sized for the load above it and made thinner at higher storeys. A brace sized for the worst case fits every module in the stack, so more modules can use the same frame.

Fig. 2.2 — Bracing elevation; same module and scale as Fig. 2.3b.

2.3 Stairs

2.3 Stairs, page 18
Page 18Enlarge
Read page 18 as text

2 . 3 Stairs

METALOQ can supply the stair using the same manufacturing process as the frame. The stair is laser-cut and brake-formed from the same steel coil, plate, and/or HSS. Supplied with or without the guardrail and handrail, it is a complete assembly that can be installed in the module at the factory or on site.

The stair is parametrically generated to suit module height and local building code: riser, tread, width, landing and guardrail height are all set to the project. Treads can be supplied with your selected finish, including anti-slip rubber or steel grating. The top and bottom treads nest, so no rework is needed at the matelines.

The main benefit of building the stair into the module is access: it gives the crew setting modules access to the setting level, accelerating the build schedule.

Fig. 2.3a — Left: section through the top landing connection. The bronze tread and plate are bolted to the module’s blue

rim channel trim beam at the landing edge. Right: a single stair flight that can be craned into the stair module.

Fig. 2.3b — Floor framing plan showing two stair openings with header beams.

2.4 Plan Views and Load Paths

2.4 Plan Views and Load Paths, page 19
Page 19Enlarge
Read page 19 as text

Fig. 2.4a — Wave product line: 12.5′ × 28′ modules around a 28′ × 28′ core.

Fig. 2.4b — Skyline product line: a mix of 10′ and 12.5′ × 27.5′ modules around a 27.5′ × 27.5′ core.

2 . 4 Plan Views and Load Paths

A module layout is governed by structural constraints requiring the load paths to transfer across corridors and around corners. Maximum efficiency is achieved when the modules are aligned, as shown in the following two examples, illustrated on the facing page.

Across the Corridor. Modules facing each other across a double-loaded corridor must align. That is, their matelines both align to the same grid, so that lateral loads are transferred cleanly across the building. Where the columns are offset (the blue arrows), the corridor must be designed to transfer those loads diagonally, which adds design complexity. Some form of this is inevitable around a corner, so focusing the transfer capacity on a single corridor frame is desirable.

At the Core. The core frames are different. This location is where the elevators and stairs are centralized, and it becomes the location where lateral and diaphragm loads transfer from the wings. Because the core may not have access to windows, it is often dedicated to vertical circulation and mechanical/electrical systems. In this case, the stair and elevator modules can be braced more heavily and frequently with cross-bracing surrounding the vertical circulation. This anchor point allows the corner modules around the outside to tie back to the core using a transfer corridor frame.

Two options for the Wave and Skyline product lines are shown for illustration:

• Wave uses two 14′ × 28′ module cores to brace a 28′-long repeated living module.

• Skyline uses a 27.5′ module depth with a 27.5′ core, so the core is two 13.75′ × 27.5′ modules, each containing a stair, elevator and/or mechanical room.

Corner Forces. The method for resolving the various loads across the module bracing is a critical aspect of the structural design, and requires analysis by a structural engineer familiar with the system described here.

READING THE PLANS

Elevator Core. The navy-coloured module is the elevator shaft, which can be heavily braced.

Stair Core. The cyan-coloured module is a stair module, up to 14′ wide, and can also be heavily braced as needed.

Aligned. A red-coloured arrow marks braced module walls that align across a corridor, so the load transfers directly across the corridor.

Near-Aligned. A blue-coloured arrow marks braced walls that require the corridor frame to act as a transfer frame.

Specialty Connection. The circle marks locations where non-standard connections are needed to align corner columns with mid-span columns.

2.5 Seismic Strategy Ladder

2.5.1 Barge and sea voyage

2.5.2 Building height

2.5 Seismic Strategy Ladder, page 20
Page 20Enlarge
Read page 20 as text

2 . 5 Seismic Strategy Ladder

The class is set by building height and the site’s seismic category (SC), so every project requires site-specific engineering. Each class is a seismic force-resisting system listed in NBC 2020 Table 4.1.8.9, as adopted by OBC 2024. Classes A and B are cold-formed steel strap-braced walls designed to CSA S136 and AISI S400. Classes C and D are conventional construction steel braced frames designed to CSA S16-19 Clause 27. Class E carries the lateral load on a separate structure.

CL ASS SEISMIC FORCE-RESISTING SYSTEM RD / RO SC1–SC2 SC3–SC4

A Conventional construction strap-braced wall (CSA S136 + AISI

1.2 / 1.3 ≤ 15 m NP

S400)

B Limited-ductility strap-braced wall (CSA S136 + AISI S400) 1.9 / 1.3 ≤ 20 m ≤ 20 m

C Conventional construction braced frame (CSA S16 27.12.1) 1.5 / 1.3 No limit ≤ 15 m

D Conventional construction braced frame over 15 m (CSA S16

27.12.4) ² 1.5 / 1.3 — (Class C

≤ 60 m (SC3),

applies)

≤ 40 m (SC4)

E Separate core or bracing tower with continuous columns; modules

per system as required > 60 m (SC3),

tied back

> 40 m (SC4)

Height limits are maximum heights above grade from NBC 2020 Table 4.1.8.9 (NP = not permitted). Rd and Ro are the NBC ductility- and overstrength- related force modification factors. In SC3–SC4, Classes C and D are limited to 15 m for assembly occupancies.

² Above 15 m (CSA S16 27.12.4; not for assembly occupancies): increased seismic forces, dynamic analysis, Class 1 or 2 beams and columns, and connections designed for 1.30 × the seismic forces. Full conditions in the Addenda.

Braced frames to CSA S16 27.5–27.8 (moderately ductile and limited-ductility concentrically braced frames, eccentrically braced frames, buckling-restrained braced frames) are not listed. Their columns, including gravity columns, must be continuous and of constant section over at least two storeys (S16 27.5.5.3, 27.1.4), which a stacked module cannot offer.

Facing page: a fourteen-storey stack with the braced end bays drawn over it. The bracing is diagrammatic. It marks which bays carry lateral load, not which member is used. The members are described in §3.7.

Barge and sea voyage

A barge voyage rated to 1.0 g (sea state ≤ 4) may require the equivalent of Class C or D temporary bracing for transport only as required by the transportation provider. This bracing is not required in service and may be released on site at the owner’s option (see Logistics).

Building height

The same classes apply to the two sections that follow. A ten-storey building is the tallest case assessed to date and typically requires Class C or D. In a tall building, the module frame is no longer the entire lateral system, and Class E applies. The height of a METALOQ building is limited by the seismic force-resisting system it may use (NBC Table 4.1.8.9): in SC3–SC4, 15 m for Class C, and up to 60 m (SC3) or 40 m (SC4) for Class D (15 m for assembly occupancies). Above that, a separate core or tower carries the lateral load (Class E). The stacked-column connections must also be checked for each building.

2.6 The Ten-Storey Building

2.6 The Ten-Storey Building, page 21
Page 21Enlarge
Read page 21 as text

2 . 6 The Ten-Storey Building

Ten storeys is the tallest METALOQ building assessed to date, for one site in Seismic Category 2. Taller buildings depend on the site’s seismic category and on a stronger stacked-column connection (see finding 5).

JEROL Technologies has assessed a ten-storey METALOQ building of 100 modules in North York, Ontario, against OBC 2024 / NBC 2020, CSA S16-19 and CSA S136-16. The upper storeys use the standard METALOQ frame. In the lower storeys, the braced-bay columns are strengthened, and the current stacked-column connections are not strong enough: a new connection detail or more bracing is required (finding 5). The report is a demonstration of the system on one building and one site, not a design or a rating for the product generally; each building requires its own engineering.

THE ASSESSED BUILDING

Report JEROL Misc. 26000, Rev. 1, 27 Oct 2026

Modules 100, ten per floor: nine dwelling and one egress

Plan Double-loaded: two rows of five modules either side of a corridor of assembled floor panels

Module · footprint · height 3.835 × 8.53 × 3.0 m · 19.2 × 19.2 m · 30.3 m

Bracing No braces on the north and south facades; braces in about 22% of the east and west walls

Seismic SC2 · site class D · IES(0.2) 0.341 · IES(1.0) 0.178

WHAT THE ASSESSMENT FOUND

1. Class C bracing is sufficient at this site. North York is in Seismic Category 2, where the NBC permits a conventional construction braced frame (Class C on the seismic ladder, Rd 1.5, Ro 1.3) with no height limit. The frame is designed for strength, without the capacity-design detailing a ductile system requires. Because IES(0.2) is below 0.35 in SC2, the enhanced connection requirements of CSA S16 27.12.2 do not apply. The same building in SC3 or SC4 would need Class D (S16 27.12.4): dynamic analysis, Class 1 or 2 beams and columns (the ribbed corner columns used here are not Class 1 or 2, so plain sections would be needed), increased seismic forces, and connections, including the stacked-column connections, designed for 1.30 times the seismic forces. 2. The upper storeys use the standard frame. No column above level 5 needs a ribbed section; at level 6 the braced-bay mid columns use the standard (unribbed) corner section. 3. The braced-bay columns of the lower storeys are strengthened. In the braced bays, the intermediate columns are replaced with corner-column sections. This is the accumulation of load described in §3.2. Levels 1 to 3 use the 76 × 99 × 298 × 6 mm ribbed corner column and levels 4 to 5 the 99 × 298 × 6 mm ribbed column; levels 6 to 10 use unribbed sections. The braces increase from 51 mm square HSS at the roof to 76 mm square HSS at the base. 4. The floors carry in-plane strap bracing. The braces are kept off the north and south facades to leave room for large windows and walk-out balconies. In exchange, the floor diaphragm needs in-plane strap bracing to deliver the lateral load to the braced walls. 5. The stacked-column connections need more tension capacity at levels 1 to 5. In the braced bays, the factored seismic tension at the stacked-column connection reaches 470 kN at level 1, against 160 kN for the current single-bolt connection. The connection has room for two tension bolts, and the dagger and bolt holes can be resized as required. Two 1″ ASTM F3125 Grade A490 bolts give about 630 kN factored tension (CSA S16 13.12.1.3), with the dagger as reserve. That leaves margin for prying at this site, and also covers the higher connection demand of about 610 kN that applies to taller buildings in SC3–SC4 (S16 27.12.4), so one detail serves both. The assessment is a demonstration of the system, not a design: each building’s stacked-column connections are designed by its own engineer, including prying action and the dagger and connected plates. More braced bays to reduce the force at each connection remain an alternative. 6. Section shape adds axial capacity more efficiently than wall thickness. A rib raises the corner column’s compressive capacity about as much as going from 6 mm to 8 mm wall (440 kN vs 435 kN), and a rib with a lip raises it further, to 745 kN (see Corner Column). For bending, thickness is more effective. The dogbone gains capacity with a higher plate grade; dagger tension is governed by the bolt grade.

The calculations behind these findings are not reproduced here. The full report is bound in as Addendum 3. Equipment loads are still to be confirmed in the report.

2.7 Tall Buildings

2.7 Tall Buildings, page 22
Page 22Enlarge
Read page 22 as text

2 . 7 Tall Buildings

In this manual, a tall building is one that exceeds what the module frame can resist on its own: above the Class D limit on the seismic ladder (60 m in SC3, 40 m in SC4), or above 30 m where the building is slender, meaning its height is more than 4 times its minimum width (dynamically sensitive under NBC 4.1.7.2). Above these limits, a separate core or tower carries the lateral load (Class E). This structural definition is separate from the fire-safety one: under NBC 3.2.6.1, a residential (Group C) building with a floor level more than 18 m above grade is a ‘high building’. A supertall METALOQ building is actually designed as a stack of mid-rise buildings. The study on the facing page illustrates six-storey METALOQ buildings stacked, each standing on its own structural shelf. The shelves hang from the cores and perimeter columns. The core carries the tower’s lateral load; the modules are tied back to it but carry their own weight. Similar strategies have been deployed internationally when designing tall modular buildings.

THE PRECEDENT

The precedent is Foster + Partners’ design for One Bloor West in Toronto, Canada’s first supertall at 85 storeys. There, a ring of eight perimeter columns and diagonal steel hangers carry the floors and leave the corners free of columns.

The METALOQ-Skyhook study keeps that structure and replaces the cast floors between shelves with a METALOQ stack. There are two resulting strategies:

• a point tower on a single central core, its eight exterior columns hanging the corners of each shelf;

• a split tower, its shelves hung between two end cores and supported by exterior columns.

WHY IT SUITS THE FRAME

1. Steel modular works efficiently at mid-rise. A six-storey stack uses a standard frame for maximum efficiency.

2. The datum resets at every shelf. Zero clearance only has to hold over six modules, never over the height of the tower.

3. The shelf above provides weather protection. It shelters the stack being set, and adds a fire and smoke separation between stacks.

4. The host structure is designed first. The concrete superstructure itself must be verified against the cumulative weight and tie-back capacity of the frames to the core.

5. Each shelf is like a new foundation. The stack bears on its shelf in the same way a building bears on its footings, and requires the same METALOQ precision. Services are deployed in six-storey distribution groups.

The tower on the facing page is a design study; its shelves, joints, and core are not yet engineered.