Why a METALOQ frame can only go together one way, and why that way is square.
A METALOQ module is a steel chassis. The perimeter is made of cold-formed steel corner columns and rim beams, infilled with light-gauge steel floor and ceiling joists. Rim beams and columns are laser-cut from coil, then brake-formed or rolled into shape, with every connection hole and slot already cut. Reinforcing plates are welded on before shipping, so assembly at your plant needs only hand tools.

Zero clearance describes the fit between every bolt and its hole. Each hole is matched to its bolt: no oversizing, no slotted holes and no play to take up. With no play, there is only one position in which a frame can be assembled, and that position is square. No jigs, fixtures or squaring frames are needed.
By comparison, a conventional connection puts a half-inch bolt through a 9/16-inch hole. That is about 1/16 inch of clearance at every connection, which can add up to a quarter inch between two adjacent frames before they leave the shop, and keeps accumulating up a stack. Matched-hole work is routine in the automotive sector, which is where this discipline comes from.

METALOQ Documentation v1.0, pages 11–14. Select a page to enlarge it.
CHAPTER
A finished METALOQ building. The frame is supplied by METALOQ, then clad and fit out by the customer.
METALOQ is a cold-formed steel (CFS) module framing system designed for light-gauge steel (LGS) wall infill. The pre-engineered “frame kit” components are mass-customized by METALOQ using specialized machinery and tooling. This removes the capital cost of steel-fabricating equipment, plant space, and trade certifications, and reduces the design and commissioning time otherwise required at the modular plant. Frames are assembled in-house or shipped knocked-down (KD) on pallets to a modular builder.
METALOQ frames:
• assemble without specialized trades or complex fixtures
• hold the precision tolerances required for a CNC-driven fit-out process
• stack to ten storeys as assessed, and higher with heavier variants and brace cores
• are non-combustible, and can be adapted to local building codes
• accommodate almost any architectural layout or massing
A METALOQ module is a rigid, self-aligning steel chassis. The perimeter structure consists of proprietary cold-formed steel (CFS, shown blue) corner columns and rim beams, infilled with LGS (shown grey) floor and ceiling joists.
The rim beams and columns are laser-cut from steel coil, then brake-formed or rolled into structural shapes. This is precision- fabricated structural steel, with the connection holes and slots already cut into each part. Components such as columns and beams have their reinforcing plates welded in place ahead of shipping, so assembly at your plant needs only hand tools.
The precision gained from this strategy allows modules to stack with effectively zero clearance. Shaped pins called daggers align the modules, and dogbone plates tie them together at the module matelines and at the corridor frames. The following diagram highlights the key members.
CLM Column 4×12 / 100×300 mm, ¼″ / 6 mm wall
RJP Rim ceiling beam 3×6.5 / 75×165 mm
RJP Rim floor beam 3×10.5 / 75×265 mm
JST Floor / ceiling joist 16 g / 1.6 mm (0.061″)
BRP Crossbrace diagonal X-brace, end frames
Left — Test stack from 2021. In a completed building the frame is fully fitted out with services, walls, cladding and finishes.
Engineering Drawings: The METALOQ design team will author a shop drawing set describing the fabrication details and BOM for each chassis.
End Elevation: corner columns, end rim beams, and end X-bracing. Side Elevation: clamped joist array and wall bracing. Plan: floor and ceiling joist layout spanning the long rim beams.
FRAME HEIGHT = 9′-10″ / 2996 mm
FRAME LENGTH = 20′-9″ / 6336 mm
FRAME WIDTH = 8′-9″ / 2678 mm
Every METALOQ model is established on a right-handed coordinate system. The origin and all dimensions are measured from the column top and bottom end plates. The front is the corridor-facing side.
• x: outside face of the left-side column bottom end plate
• y: outside face of the front-side column bottom end plate
• z: bottom face of the column bottom end plate
• floor level: the top of the floor deck; dimension to floor level = beam depth plus deck thickness.
• width: between the outsides of the front column bottom end plates
• depth (also called length): between the front and back column bottom end plates
• height: between the column bottom and top end plates, the same dimension as floor-to-floor
All drawings and communications reference this agreed-upon datum, including architectural, engineering and construction (AEC) drawings for the base building, BIM module coordination, and shop and fabrication drawings. Base building and modules must agree on it. See §1.3 for how zero-clearance tolerances propagate through the module and across the stack. If the datum is not established, the models diverge and the error is not found until the steel arrives on site. At that stage it affects the site schedule and budget, and so it should be established once at the start of the project.
The factory datum is the module’s own 0-0-0, fixed to the frame and travelling with it. The architectural grid matches this datum. The module’s left side is established from its corridor side: standing in the corridor looking at the module, the datum is on the left. See diagram below.
The 0-0-0 datum must be locatable in the physical frame, not only in the model. METALOQ frames have a true square 90° outside corner, with no radius or chamfer, and the column top and bottom end plates meet at the mateline with no gap between modules. A tape measure or total station can be set directly on the frame: there is no locating-pin centre to work back from and no cover gap to deduct, so the dimension measured on site matches the dimension modelled. The top end plate at this corner is thickened and recessed to receive the dogbone that ties the four meeting modules together.
DESIGN RULE 0-0-0 is the grid
The 0-0-0 datum is the single point at which METALOQ shop drawings, structural analysis models, architectural BIM, and foundation layouts agree. Establish the agreed gridlines before any modelling.
DESIGN RULE One building origin, fixed
The building origin aligns with the module grids at the bottom-left corner. The preferred convention is lettered grid lines along the top and numbered lines down the side.
Fig. 1.2 — six bays of a double-loaded corridor. Red rectangles outline one module in each row; the bold cross symbol is that module’s factory 0-0-0, the left side when viewed from the corridor. The corridor frames (bronze) align with the same 0-0-0 grid.
Zero clearance describes the fit between every bolt and its hole. In a METALOQ frame, each bolt hole is matched to its bolt: there is no oversizing, no slotted holes, and no clearance to take up. This ensures the frame self-squares and self-aligns during assembly. The result is a stack that is square, aligned, and dimensionally consistent with the model. This level of accuracy is required to stack module frames tall and wide without tolerance build-up at the matelines, in both the horizontal and vertical directions.
With no play at the holes, there is only one position in which a frame can be assembled, and that position is square. A frame that is out of true is pulled square as its diagonal brace is bolted home. Squareness is therefore a property of the components: no jigs, fixtures, squaring frames, or bolt-to-bolt measurement are required. It is recommended that frames are built on a flat, horizontal surface to keep other elements, such as the wall frames, plumb.
By comparison, the industry-standard connection uses a ½″ bolt through a 9/16″ hole, which carries approximately 1/16″ of clearance at every connection: roughly 1/8″ of possible movement within one frame, and up to a quarter-inch between two adjacent frames, before the components leave the shop. These tolerances accumulate along a module and up a stack. The zero-clearance approach leaves nothing to accumulate. Matched-hole work is a tooling discipline rather than a structural- steel discipline, and it is used routinely by fabricators in the automotive sector.
The same principle carries across the joint. Modules register face-to-face and top-to-bottom at the top and bottom end plates of each column: the tapered dogbone pulls the plates together horizontally, and the dagger pulls them together vertically. As each module is set, the daggers at its columns align it with the module below, so the stack aligns itself. Alignment is carried by structural hardware.
Zero clearance gives three outcomes that this manual relies on throughout:
1. A module’s external dimension is its grid dimension. There are no tolerance shims or spacers to add. 2. Dogbones and daggers ensure alignment from the foundation up, so foundation accuracy governs the whole stack. 3. Diaphragm continuity across modules is achieved by the dogbone plate acting between top end plates.
The dogbone plate is set into the recessed pocket of the top end plate, and its tapered depth pulls the two modules tight.
This section is an orientation to the METALOQ system. It does not replace project-specific architecture or engineering, and nothing here should be relied on to design a building. Every project needs licensed professionals and the approval of the authorities having jurisdiction. Illustrations are not to scale.