The assessment by JEROL Technologies.
METALOQ Documentation v1.0, pages 83–103. Select a page to enlarge it.
Client Project: --- Jerol Project: Misc. 26000
Page 1
27/10/2026 – Rev. 1
Rev. 1 – 27 October 2026 (supersedes the issue of 9 October 2026)
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 2
27/10/2026 – Rev. 1
Prepared by:
Date: 09/10/2026
Verified & Approved by: Date: 09/10/2026
Rev. 0 09/10/2026 Issued.
Rev. 1 27/10/2026 Reissued with the METALOQ Product Manual review: client name corrected (p.4); braced-bay column wording and section reference corrected, and stacked-column connection upgrade added (p.18); lateral system table revised for modular construction and conventional construction limits in SC3–SC4 (p.29); lower rim joist label corrected to 75x265 (p.40); roof joist section label corrected to 600S162-43 (p.41).
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 3
27/10/2026 – Rev. 1
1. Introduction ...........................................................................................................4
2. Applicable Codes and Standards ................................................................................4
3. Loading ...........................................................................................................4 a. Methodology b. Dead Load c. Equipment Loads d. Transportation Loads e. Live Load f. Seismic Load g. Snow Load h. Wind Load i. References & Software
4. Structural Framing Description .................................................................................18
5. Load Cases & Load Combinations .................................................................................20
6. Structural Model ..............................................................................................22
7. Member Summary ...................................................................................................28
8. Connections capacities improvement table .............................................................40
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 4
27/10/2026 – Rev. 1
prospective 10 story, 100 modules residential building to be located in North York, ON. Review and calculations were based on documentation provided by client .
Building code: Ontario Building Code 2024 / National Building Code 2020 Design of Rolled and Closed shapes: CSA S16 Design Cold formed open shapes: CSA S136 Structural Steel Materials: CSA G40.20 /G40.21 Design of Foundation pads: CSA A23.3 Concrete Materials: CSA A23.1/A23.2
y
A strictly vertical lift is assumed for the lifting scenario with the lugs being the only points of contact between the structure and the lifting apparatus. All provided lifting lugs on each side must be used for any lifting. As indicated in literature review, the airflow over a tractor trailer has characteristics similar to airflow over a low rise building.(1,2) Limit states design approach is used for all main members in all load cases except where noted. As indicated by previous point, Allowable stress design approach is used for critical connection points tied to lifting points. (5)
y y
y
Dead load -Self weight of steel members. - 1.0kPa Floor dead load - 0.75 kPa Roof dead - 1.0 kPa Stud walls - 0.25 kPa Roof Coll.
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 5
27/10/2026 – Rev. 1
TBC
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 6
27/10/2026 – Rev. 1
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 7
27/10/2026 – Rev. 1
Seismic Input Summary
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 8
27/10/2026 – Rev. 1
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 9
27/10/2026 – Rev. 1
Seismic Results
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 10
27/10/2026 – Rev. 1
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 11
27/10/2026 – Rev. 1
Snow Input
Snow Results
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 12
27/10/2026 – Rev. 1
Wind Input
H 30.3 m
Cgclad 2.5
= Ce 1.25
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 17
27/10/2026 – Rev. 1
Moverturningwindx = Windshearx H
2 ⎛⎝ 1.053 104 ⎞⎠ kN m
= Windshearz 694.792 kN = Moverturningwindz ⎛⎝ 1.053 104 ⎞⎠ kN m
= Windshearx 694.792 kN = Moverturningwindx ⎛⎝ 1.053 104 ⎞⎠ kN m
-Software:
1. Structural Analysis & Code Checks of Hot Rolled Members: RISA-3D Version 8.1.3
2. Foundation Loads & Checks : Mathcad Prime Version 10.0
3. Module Anchor Capacity : Hilti PROFIS Anchor Version 2.5.2
4. Foundation Tables: Microsoft Excel 2021
-References:
1. Baker, C. J., “Ground Vehicles in High Cross Winds,” Parts I, II and III. Journal of Fluids and Structures (1991) 5, 69-90. Academic Press Limited.
2. Coleman, S. A., and Baker, C. J., “An Experimental Study of the Aerodynamic Behavior of High Sided Lorries in Cross Winds,” Journal of Wind Engineering and Industrial Aerodynamics, 53 (1994) 401-429. Elsevier Science Publishers B.V., Amsterdam.
3.Packer, Jeffrey A. Hollow Structural Section Connections And Trusses. Toronto: Canadian Inst Of Steel, 1997. Print.
4. Ontario Government,. Occupational Health And Safety Act ONTARIO REGULATION 213/91 CONSTRUCTION PROJECTS. Toronto: Queen's Printer for Ontario, 2015. Print..
5.ITWBuildex,. Product Catalog. 1st ed. Itasca: ITW Buildex and Illinois Tool Works, Inc, 2010. Print.
6.Canadian Commission On Building And Fire Codes,. User's Guide NBC 2010 Structural Commentaries (Part 4 Of Division B). Ottawa: Institute for Research in Construction National Research Council Canada, 2011. Print.
7.Coduto, Donald P. Geotechnical Engineering. Upper Saddle River, NJ: Prentice Hall, 1999. Print.
8. The Crosby Group,. 'Home - The Crosby Group'. N.p., 2015. Web. 7 May 2015.
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 18
27/10/2026 – Rev. 1
The proposed building is a 10-storey residential structure with a plan footprint of 19.2 m by 19.2m and an overall height of 30.3 m.
Each floor consists of ten prefabricated Metaloq modules, arranged as shown in Figure 1:
Nine residential (dwelling) modules, each measuring 3.835 m wide × 8.53 m long × 3.0 m high. One egress module, measuring 3.835 m wide × 8.53 m long × 3.0 m high, which accommodates the elevator shaft, stairwell, and means of egress. A corridor made of assembled floor panels provides egress to the elevator and stairwell.
The maximum unsupported span of the rim joists is 4.26m, while the minimum unsupported span is 2.0 m.
The primary lateral force-resisting system comprises concentrically braced bays arranged symmetrically within the modules. In the longitudinal direction of the modules, the braced bays are 4.20 m wide for a total of 8 pairs of braces distributed symmetrically. In the transverse direction, the braced bay are 2m wide, with ten pairs of braces distributed symmetrically. For the braced bays of levels 1 to 6, the Metaloq mid columns are not adequate to support the compressive loads from the factored lateral cases. Corner column sections must be provided on each side of the bay bracing for adequate load support; ribbed sections are required at levels 1 to 5.
On the South and North facade elevations, no braces are present to allow for large window openings and/or walk out balconies. For the East and West facade elevations, braces are limited to about 22% of the wall areas, thus leaving room for large openings on those facades.
The bracing layout has been developed to provide large opportunities for openings on the facades, therefore in plane strap bracing is required for proper diaphragm actions.
As discussed in Section 3 of this report, the project site is classified as Seismic Category 2. For this level of seismic demand and the proposed building height, conventional concentrically braced steel construction is an acceptable lateral force-resisting system. Accordingly, the structural members and their connections have been designed using strength-based design principles.
The tensile forces at the stacked-column connections of the braced bays from level 1 to level 5 exceed the capacity of the typical and improved connections listed in section 8 of this report (470 kN at level 1, against 160 kN for the standard single M20 bolt). The connection has room for two tension bolts, and the dagger and bolt holes can be resized: two 1" ASTM F3125 Grade A490 bolts provide about 630 kN factored tension (CSA S16-19 13.12.1.3), with the dagger as reserve, subject to prying action and checks of the dagger and connected plates. The alternative is to provide more bracing to further spread the lateral loads.
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 19
27/10/2026 – Rev. 1
Figure 1: Module types
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 20
27/10/2026 – Rev. 1
LC # Description 1 Seismic Wgt 2 Dead 3 Live / Equipment 4 Snow 5 Wind X 6 Wind -X 7 Wind Z 8 Wind -Z 9 EX 10 E-X 11 EZ 12 E-Z 13 EX + ECC 14 EX-ECC 15 EZ + ECC 16 EZ - ECC
18 1.25 DL + 1.5 LL + 1.5 Equipment + 1.0 SL + 1.4 Wind X 19 1.25 DL + 1.5 LL + 0.5 SL + 1.4 Wind- X 20 1.25 DL + 1.5 LL + 1.5 Equipment + 1.0 SL + 1.4 Wind Z 21 1.25 DL + 1.5 LL + 1.5 Equipment + 1.0 SL + 1.4 Wind- Z 22 1.25 DL + 1.0 LL + 1.0 Equipment + 1.5 SL +0.4 Wind X 23 1.25 DL + 1.0 LL + 1.0 Equipment + 1.5 SL + 0.4 Wind- X 24 1.25 DL + 1.0 LL + 1.0 Equipment + 1.5 SL +0.4 Wind Z 25 1.25 DL + 1.0 LL + 1.0 Equipment + 1.5 SL +0.4 Wind- Z 26 1.25 DL + 1.0 LL + 1.0 Equipment + 1.5 SL 27 1.25 DL + 1.5 LL + 1.5 Equipment + 1.0 SL 28 1 DL + 0.5 LL + 0.5 Equipment + 0.25 SL + EX 29 1 DL + 0.5 LL + 0.5 Equipment + 0.25 SL + EX + ECC 30 1 DL + 0.5 LL + 0.5 Equipment + 0.25 SL + EX- ECC 31 1 DL + 0.5 LL + 0.5 Equipment + 0.25 SL + EZ 32 1 DL + 0.5 LL + 0.5 Equipment + 0.25 SL + EZ + ECC 33 1 DL + 0.5 LL + 0.5 Equipment + 0.25 SL + EZ- ECC 34 0.9 DL + 1.4 Wind X 35 0.9*DL + 1.4 Wind -X 36 0.9 DL + 1.4 Wind Z 37 0.9*DL + 1.4 Wind -Z 38 Dead + Live + Equipment + Service Snow 39 1DL + EX 40 1DL EX
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 21
27/10/2026 – Rev. 1
40 1DL - EX 41 1DL + EZ 42 1DL - EZ 43 1DL + EX + ECC 44 1DL + EX-ECC 45 1DL + EZ + ECC 46 1DL + EZ - ECC 47 1DL + Service WIND X 48 1DL + Service WIND -X 49 1DL + Service WIND Z 50 1DL + Service WIND -Z 51 Live + Service Snow 52 1.25 DL + 1.5 Live + 1.5 Equipment + 0.5 Snow 53 1 DL + Live + Equipment + Service Snow 54 1DL + EX DriŌ 55 1DL - EX DriŌ 56 1DL + EZ DriŌ 57 1DL - EZ DriŌ Table 1. LC List
Note: Internal Pressures taken into account in principal wind cases
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 22
27/10/2026 – Rev. 1
Figure 2: Isoview framing
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 23
27/10/2026 – Rev. 1
Figure 3: Side view 1
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 24
27/10/2026 – Rev. 1
Figure 4: Side view 2
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 25
27/10/2026 – Rev. 1
Figure 5: Iso view section set
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 26
27/10/2026 – Rev. 1
Figure 6: Plan view bracing layout
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 27
27/10/2026 – Rev. 1
Figure 7: Plan view foundation
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 28
27/10/2026 – Rev. 1
Figure 8: Iso view Module general arrangement
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 29
27/10/2026 – Rev. 1
Offers limited energy dissipation. Not suitable for modular: columns, incl. gravity columns, must be continuous and of constant section over a minimum of two storeys (S16 27.5.5.3, 27.1.4)
Not applicable
Viable for SC1 and SC2 at any height. SC3 and SC4: see note 1 below
Note 1 – Conventional construction braced frame in SC3 and SC4: up to 15 m (CSA S16-19 27.12.1), or up to 60 m in SC3 and 40 m in SC4 under CSA S16-19 27.12.4 (dynamic analysis; Class 1 or 2 beams and columns; seismic forces increased 2 % per metre above 15 m; columns and connections designed for 1.30 times the seismic forces). Not above 15 m for assembly occupancies (NBC 2020 Table 4.1.8.9).
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 30
27/10/2026 – Rev. 1
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 31
27/10/2026 – Rev. 1
Figure 9: Iso view East West Corridor bracing
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 32
27/10/2026 – Rev. 1
Figure 10: Iso view North South bracing
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 33
27/10/2026 – Rev. 1
Figure 11: Iso view Diaphragm Eccentricities
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 34
27/10/2026 – Rev. 1
Figure 12: Plan view governing North South Wind load
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 35
27/10/2026 – Rev. 1
Figure 13: Plan view governing East West Wind load
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 36
27/10/2026 – Rev. 1
Figure 14: Plan view governing North South Eccentric Seismic load
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 37
27/10/2026 – Rev. 1
Figure 15: Plan view governing East West Eccentric Seismic load
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 38
27/10/2026 – Rev. 1
Figure 16: Plan view Diaphragm strap bracing
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 39
27/10/2026 – Rev. 1
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 40
27/10/2026 – Rev. 1
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
Client Project: --- Jerol Project: Misc. 26000
Page 41
27/10/2026 – Rev. 1
Section
600S162-43 (43 mil, 1.15
mm)
95 Allaura Blvd Aurora, Ontario L4G 3N2
Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca
This section is an orientation to the METALOQ system. It does not replace project-specific architecture or engineering, and nothing here should be relied on to design a building. Every project needs licensed professionals and the approval of the authorities having jurisdiction. Illustrations are not to scale.