Addendum 3 — Ten-Storey Structural Calculation

Addendum 3 — Ten-Storey Structural Calculation, page 83
Page 83Enlarge
Read page 83 as text

Client Project: --- Jerol Project: Misc. 26000

Page 1

27/10/2026 – Rev. 1

Structural Calculation

10 Storeys / 100 Modules Metaloq North York, ON

Rev. 1 – 27 October 2026 (supersedes the issue of 9 October 2026)

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 2

27/10/2026 – Rev. 1

Prepared by:

Date: 09/10/2026

Verified & Approved by: Date: 09/10/2026

Revision history

Rev. 0 09/10/2026 Issued.

Rev. 1 27/10/2026 Reissued with the METALOQ Product Manual review: client name corrected (p.4); braced-bay column wording and section reference corrected, and stacked-column connection upgrade added (p.18); lateral system table revised for modular construction and conventional construction limits in SC3–SC4 (p.29); lower rim joist label corrected to 75x265 (p.40); roof joist section label corrected to 600S162-43 (p.41).

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 84, page 84
Page 84Enlarge
Read page 84 as text

Client Project: --- Jerol Project: Misc. 26000

Page 3

27/10/2026 – Rev. 1

Table of Contents:

1. Introduction ...........................................................................................................4

2. Applicable Codes and Standards ................................................................................4

3. Loading ...........................................................................................................4 a. Methodology b. Dead Load c. Equipment Loads d. Transportation Loads e. Live Load f. Seismic Load g. Snow Load h. Wind Load i. References & Software

4. Structural Framing Description .................................................................................18

5. Load Cases & Load Combinations .................................................................................20

6. Structural Model ..............................................................................................22

7. Member Summary ...................................................................................................28

8. Connections capacities improvement table .............................................................40

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 4

27/10/2026 – Rev. 1

1. Introduction

Jerol Technologies Inc. was retained by Metaloq Inc. to provide a structural review of a

prospective 10 story, 100 modules residential building to be located in North York, ON. Review and calculations were based on documentation provided by client .

2. Applicable Codes and standards

Building code: Ontario Building Code 2024 / National Building Code 2020 Design of Rolled and Closed shapes: CSA S16 Design Cold formed open shapes: CSA S136 Structural Steel Materials: CSA G40.20 /G40.21 Design of Foundation pads: CSA A23.3 Concrete Materials: CSA A23.1/A23.2

3. Loading

a. Methodology

y

A strictly vertical lift is assumed for the lifting scenario with the lugs being the only points of contact between the structure and the lifting apparatus. All provided lifting lugs on each side must be used for any lifting. As indicated in literature review, the airflow over a tractor trailer has characteristics similar to airflow over a low rise building.(1,2) Limit states design approach is used for all main members in all load cases except where noted. As indicated by previous point, Allowable stress design approach is used for critical connection points tied to lifting points. (5)

y y

y

b. Dead load

Dead load -Self weight of steel members. - 1.0kPa Floor dead load - 0.75 kPa Roof dead - 1.0 kPa Stud walls - 0.25 kPa Roof Coll.

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 85, page 85
Page 85Enlarge
Read page 85 as text

Client Project: --- Jerol Project: Misc. 26000

Page 5

27/10/2026 – Rev. 1

c. Equipment Loads

TBC

d. Transportation Loads

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 6

27/10/2026 – Rev. 1

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 86, page 86
Page 86Enlarge
Read page 86 as text

Client Project: --- Jerol Project: Misc. 26000

Page 7

27/10/2026 – Rev. 1

e. Live load

Live load 1.0 kPa on roof 1.9 kPa in dwelling units 4.8 kPa for halls & stairs

f. Seismic Load

Seismic Input Summary

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 8

27/10/2026 – Rev. 1

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 87, page 87
Page 87Enlarge
Read page 87 as text

Client Project: --- Jerol Project: Misc. 26000

Page 9

27/10/2026 – Rev. 1

Seismic Results

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 10

27/10/2026 – Rev. 1

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 88, page 88
Page 88Enlarge
Read page 88 as text

Client Project: --- Jerol Project: Misc. 26000

Page 11

27/10/2026 – Rev. 1

g. Snow load

Snow Input

Snow Results

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 12

27/10/2026 – Rev. 1

h. Wind load

Wind Input

H 30.3 m

Cgclad 2.5

= Ce 1.25

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 89, page 89
Page 89Enlarge
Page 90, page 90
Page 90Enlarge
Page 91, page 91
Page 91Enlarge
Read page 91 as text

Client Project: --- Jerol Project: Misc. 26000

Page 17

27/10/2026 – Rev. 1

Moverturningwindx = Windshearx H

2 ⎛⎝ 1.053 104 ⎞⎠ kN m

= Windshearz 694.792 kN = Moverturningwindz ⎛⎝ 1.053 104 ⎞⎠ kN m

= Windshearx 694.792 kN = Moverturningwindx ⎛⎝ 1.053 104 ⎞⎠ kN m

i. References & Software

-Software:

1. Structural Analysis & Code Checks of Hot Rolled Members: RISA-3D Version 8.1.3

2. Foundation Loads & Checks : Mathcad Prime Version 10.0

3. Module Anchor Capacity : Hilti PROFIS Anchor Version 2.5.2

4. Foundation Tables: Microsoft Excel 2021

-References:

1. Baker, C. J., “Ground Vehicles in High Cross Winds,” Parts I, II and III. Journal of Fluids and Structures (1991) 5, 69-90. Academic Press Limited.

2. Coleman, S. A., and Baker, C. J., “An Experimental Study of the Aerodynamic Behavior of High Sided Lorries in Cross Winds,” Journal of Wind Engineering and Industrial Aerodynamics, 53 (1994) 401-429. Elsevier Science Publishers B.V., Amsterdam.

3.Packer, Jeffrey A. Hollow Structural Section Connections And Trusses. Toronto: Canadian Inst Of Steel, 1997. Print.

4. Ontario Government,. Occupational Health And Safety Act ONTARIO REGULATION 213/91 CONSTRUCTION PROJECTS. Toronto: Queen's Printer for Ontario, 2015. Print..

5.ITWBuildex,. Product Catalog. 1st ed. Itasca: ITW Buildex and Illinois Tool Works, Inc, 2010. Print.

6.Canadian Commission On Building And Fire Codes,. User's Guide NBC 2010 Structural Commentaries (Part 4 Of Division B). Ottawa: Institute for Research in Construction National Research Council Canada, 2011. Print.

7.Coduto, Donald P. Geotechnical Engineering. Upper Saddle River, NJ: Prentice Hall, 1999. Print.

8. The Crosby Group,. 'Home - The Crosby Group'. N.p., 2015. Web. 7 May 2015.

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 18

27/10/2026 – Rev. 1

4. Structural Framing Description

The proposed building is a 10-storey residential structure with a plan footprint of 19.2 m by 19.2m and an overall height of 30.3 m.

Each floor consists of ten prefabricated Metaloq modules, arranged as shown in Figure 1:

Nine residential (dwelling) modules, each measuring 3.835 m wide × 8.53 m long × 3.0 m high. One egress module, measuring 3.835 m wide × 8.53 m long × 3.0 m high, which accommodates the elevator shaft, stairwell, and means of egress. A corridor made of assembled floor panels provides egress to the elevator and stairwell.

The maximum unsupported span of the rim joists is 4.26m, while the minimum unsupported span is 2.0 m.

The primary lateral force-resisting system comprises concentrically braced bays arranged symmetrically within the modules. In the longitudinal direction of the modules, the braced bays are 4.20 m wide for a total of 8 pairs of braces distributed symmetrically. In the transverse direction, the braced bay are 2m wide, with ten pairs of braces distributed symmetrically. For the braced bays of levels 1 to 6, the Metaloq mid columns are not adequate to support the compressive loads from the factored lateral cases. Corner column sections must be provided on each side of the bay bracing for adequate load support; ribbed sections are required at levels 1 to 5.

On the South and North facade elevations, no braces are present to allow for large window openings and/or walk out balconies. For the East and West facade elevations, braces are limited to about 22% of the wall areas, thus leaving room for large openings on those facades.

The bracing layout has been developed to provide large opportunities for openings on the facades, therefore in plane strap bracing is required for proper diaphragm actions.

As discussed in Section 3 of this report, the project site is classified as Seismic Category 2. For this level of seismic demand and the proposed building height, conventional concentrically braced steel construction is an acceptable lateral force-resisting system. Accordingly, the structural members and their connections have been designed using strength-based design principles.

The tensile forces at the stacked-column connections of the braced bays from level 1 to level 5 exceed the capacity of the typical and improved connections listed in section 8 of this report (470 kN at level 1, against 160 kN for the standard single M20 bolt). The connection has room for two tension bolts, and the dagger and bolt holes can be resized: two 1" ASTM F3125 Grade A490 bolts provide about 630 kN factored tension (CSA S16-19 13.12.1.3), with the dagger as reserve, subject to prying action and checks of the dagger and connected plates. The alternative is to provide more bracing to further spread the lateral loads.

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 92, page 92
Page 92Enlarge
Read page 92 as text

Client Project: --- Jerol Project: Misc. 26000

Page 19

27/10/2026 – Rev. 1

Figure 1: Module types

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 20

27/10/2026 – Rev. 1

5. Load Cases & Load combinations

LC # Description 1 Seismic Wgt 2 Dead 3 Live / Equipment 4 Snow 5 Wind X 6 Wind -X 7 Wind Z 8 Wind -Z 9 EX 10 E-X 11 EZ 12 E-Z 13 EX + ECC 14 EX-ECC 15 EZ + ECC 16 EZ - ECC

18 1.25 DL + 1.5 LL + 1.5 Equipment + 1.0 SL + 1.4 Wind X 19 1.25 DL + 1.5 LL + 0.5 SL + 1.4 Wind- X 20 1.25 DL + 1.5 LL + 1.5 Equipment + 1.0 SL + 1.4 Wind Z 21 1.25 DL + 1.5 LL + 1.5 Equipment + 1.0 SL + 1.4 Wind- Z 22 1.25 DL + 1.0 LL + 1.0 Equipment + 1.5 SL +0.4 Wind X 23 1.25 DL + 1.0 LL + 1.0 Equipment + 1.5 SL + 0.4 Wind- X 24 1.25 DL + 1.0 LL + 1.0 Equipment + 1.5 SL +0.4 Wind Z 25 1.25 DL + 1.0 LL + 1.0 Equipment + 1.5 SL +0.4 Wind- Z 26 1.25 DL + 1.0 LL + 1.0 Equipment + 1.5 SL 27 1.25 DL + 1.5 LL + 1.5 Equipment + 1.0 SL 28 1 DL + 0.5 LL + 0.5 Equipment + 0.25 SL + EX 29 1 DL + 0.5 LL + 0.5 Equipment + 0.25 SL + EX + ECC 30 1 DL + 0.5 LL + 0.5 Equipment + 0.25 SL + EX- ECC 31 1 DL + 0.5 LL + 0.5 Equipment + 0.25 SL + EZ 32 1 DL + 0.5 LL + 0.5 Equipment + 0.25 SL + EZ + ECC 33 1 DL + 0.5 LL + 0.5 Equipment + 0.25 SL + EZ- ECC 34 0.9 DL + 1.4 Wind X 35 0.9*DL + 1.4 Wind -X 36 0.9 DL + 1.4 Wind Z 37 0.9*DL + 1.4 Wind -Z 38 Dead + Live + Equipment + Service Snow 39 1DL + EX 40 1DL EX

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 93, page 93
Page 93Enlarge
Read page 93 as text

Client Project: --- Jerol Project: Misc. 26000

Page 21

27/10/2026 – Rev. 1

40 1DL - EX 41 1DL + EZ 42 1DL - EZ 43 1DL + EX + ECC 44 1DL + EX-ECC 45 1DL + EZ + ECC 46 1DL + EZ - ECC 47 1DL + Service WIND X 48 1DL + Service WIND -X 49 1DL + Service WIND Z 50 1DL + Service WIND -Z 51 Live + Service Snow 52 1.25 DL + 1.5 Live + 1.5 Equipment + 0.5 Snow 53 1 DL + Live + Equipment + Service Snow 54 1DL + EX DriŌ 55 1DL - EX DriŌ 56 1DL + EZ DriŌ 57 1DL - EZ DriŌ Table 1. LC List

Note: Internal Pressures taken into account in principal wind cases

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 22

27/10/2026 – Rev. 1

6. Structural Model

Figure 2: Isoview framing

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 94, page 94
Page 94Enlarge
Read page 94 as text

Client Project: --- Jerol Project: Misc. 26000

Page 23

27/10/2026 – Rev. 1

Figure 3: Side view 1

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 24

27/10/2026 – Rev. 1

Figure 4: Side view 2

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 95, page 95
Page 95Enlarge
Read page 95 as text

Client Project: --- Jerol Project: Misc. 26000

Page 25

27/10/2026 – Rev. 1

Figure 5: Iso view section set

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 26

27/10/2026 – Rev. 1

Figure 6: Plan view bracing layout

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 96, page 96
Page 96Enlarge
Read page 96 as text

Client Project: --- Jerol Project: Misc. 26000

Page 27

27/10/2026 – Rev. 1

Figure 7: Plan view foundation

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 28

27/10/2026 – Rev. 1

7. Member Summary

a. Gravity members

Figure 8: Iso view Module general arrangement

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 97, page 97
Page 97Enlarge
Read page 97 as text

Client Project: --- Jerol Project: Misc. 26000

Page 29

27/10/2026 – Rev. 1

b. Lateral system

Offers limited energy dissipation. Not suitable for modular: columns, incl. gravity columns, must be continuous and of constant section over a minimum of two storeys (S16 27.5.5.3, 27.1.4)

Not applicable

Viable for SC1 and SC2 at any height. SC3 and SC4: see note 1 below

Note 1 – Conventional construction braced frame in SC3 and SC4: up to 15 m (CSA S16-19 27.12.1), or up to 60 m in SC3 and 40 m in SC4 under CSA S16-19 27.12.4 (dynamic analysis; Class 1 or 2 beams and columns; seismic forces increased 2 % per metre above 15 m; columns and connections designed for 1.30 times the seismic forces). Not above 15 m for assembly occupancies (NBC 2020 Table 4.1.8.9).

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 30

27/10/2026 – Rev. 1

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 98, page 98
Page 98Enlarge
Read page 98 as text

Client Project: --- Jerol Project: Misc. 26000

Page 31

27/10/2026 – Rev. 1

Figure 9: Iso view East West Corridor bracing

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 32

27/10/2026 – Rev. 1

Figure 10: Iso view North South bracing

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 99, page 99
Page 99Enlarge
Read page 99 as text

Client Project: --- Jerol Project: Misc. 26000

Page 33

27/10/2026 – Rev. 1

c. Diaphragm

Figure 11: Iso view Diaphragm Eccentricities

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 34

27/10/2026 – Rev. 1

Figure 12: Plan view governing North South Wind load

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 100, page 100
Page 100Enlarge
Read page 100 as text

Client Project: --- Jerol Project: Misc. 26000

Page 35

27/10/2026 – Rev. 1

Figure 13: Plan view governing East West Wind load

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 36

27/10/2026 – Rev. 1

Figure 14: Plan view governing North South Eccentric Seismic load

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 101, page 101
Page 101Enlarge
Read page 101 as text

Client Project: --- Jerol Project: Misc. 26000

Page 37

27/10/2026 – Rev. 1

Figure 15: Plan view governing East West Eccentric Seismic load

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 38

27/10/2026 – Rev. 1

Figure 16: Plan view Diaphragm strap bracing

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 102, page 102
Page 102Enlarge
Read page 102 as text

Client Project: --- Jerol Project: Misc. 26000

Page 39

27/10/2026 – Rev. 1

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Client Project: --- Jerol Project: Misc. 26000

Page 40

27/10/2026 – Rev. 1

8. Connections Capacities improvement tables

Lower rimjoist 75x265 with 3" lip

95 Allaura Blvd Aurora, Ontario L4G 3N2

Phone: 905-726-3817 Fax: 905-726-9690 E-Mail: info@jerol.ca

Page 103, page 103
Page 103Enlarge
Read page 103 as text

Client Project: --- Jerol Project: Misc. 26000

Page 41

27/10/2026 – Rev. 1

Section

600S162-43 (43 mil, 1.15

mm)

95 Allaura Blvd Aurora, Ontario L4G 3N2